UPS
This guide covers enabling UPS (uninterruptible power supply) support on a braid NAS via NUT (Network UPS Tools).
Enabling UPS support (braid.enable = true plus braid.ups.enable = true)
turns on three behaviors:
- Orderly poweroff on low battery. When the UPS reports critical, NUT’s
upsmoninvokessystemctl poweroff. systemd unwindsbraid-online.service’s ExecStop, which runsbraid lockand cleanly unmounts the pool before the battery exhausts. - Preflight refusal without verified utility power.
braid add/remove/remove-missing/replacecheck UPS state at startup and refuse to begin a pool mutation unless the UPS reports verified utility power (OL). This narrows the surface that journal recovery needs to cover. - Live state visibility.
braid ups status(and the TUI Data tab) show the parsedupscoutput: status flags, battery charge, runtime remaining, load, estimated watts, input voltage, and device info.
Scope
v1 supports a single USB-connected UPS on the NAS, monitored by the NAS itself (single-host standalone). Non-USB drivers work through the escape hatch but are not tested.
Minimal config
# configuration.nix
{
braid = {
enable = true;
ups.enable = true;
};
}
Defaults: name = "ups", driver = "usbhid-ups", port = "auto". Rebuild
and plug the UPS’s USB cable in; NUT’s auto-detect finds the device.
Override the driver or port for non-USB UPSes:
braid = {
enable = true;
ups = {
enable = true;
name = "myups";
driver = "apcsmart";
port = "/dev/ttyS0";
};
};
Checking status
# Curated human summary
sudo braid ups status
# Machine-readable JSON (stable shape for scripts)
sudo braid ups status --json | jq .
Example human output:
UPS: ups
Status: OL
Battery: 100%
Runtime: 30m 0s
Load: 17% (56 W estimated)
Input: 120.0 V (transfer 88-142 V)
Device: APC Back-UPS ES 550G
Battery manufactured: 2023/04/12
Last test: Done and passed
The watts line is labeled estimated and omitted entirely if the UPS
does not report both ups.load and ups.realpower.nominal.
The --json output serializes the full parsed model. Distinct error
sentinels are emitted for the common non-OK cases:
| Condition | JSON shape | Exit code |
|---|---|---|
UPS reachable with populated ups.status | serialized UpscOutput | 0 |
UPS reachable but ups.status empty | serialized UpscOutput plus "warning": "ups_status_empty" | 0 |
| UPS query failed | {"error": "query_failed", "detail": "exit <code>: <stderr>"} | 1 |
| UPS invocation failed (upsc could not run – missing on PATH, killed by signal, or other runner-level failure) | {"error": "invocation_failed", "detail": "command failed: upsc ups: <reason>"} | 1 |
| UPS not enabled | {"error": "ups_not_enabled"} | 0 |
TUI UPS panel
braid tui’s Data tab gains a UPS row when UPS support is enabled.
Status text is color-coded by severity:
- Green – OL (on utility power).
- Yellow – OB (on battery, not yet critical).
- Red – LB / TESTFAIL / COMMBAD / FSD (critical; shutdown imminent or comms-loss).
- DarkGray – UPS query failed, or no UPS state available yet.
The panel polls on the same 5-second cadence as the
TUI fans panel. Press r to refresh both
pool and UPS probes immediately.
What happens on low battery
upsmonseesups.status: OB LB, declares the UPS critical.upsmonruns its configuredSHUTDOWNCMD. braid overrides the nixpkgs default (shutdown now) withsystemctl poweroff.- systemd walks its shutdown sequence.
braid-online.servicestops with ExecStop runningbraid lock, which unmounts the pool and closes LUKS. - The host powers off before the battery exhausts.
Under the default upsmon timings (POLLFREQ = POLLFREQALERT = 5,
FINALDELAY = 5) the window between LB detection and poweroff is
~10 seconds, plus however long braid lock takes. The default
battery.runtime.low in most UPS drivers is around 120 seconds, which
is enough headroom for a single-disk pool’s clean teardown. Larger
pools may need a wider battery.runtime.low (set at the NUT level,
not through braid).
Mutation refusal when utility power is not verified
With UPS enabled, braid add / remove / remove-missing / replace
refuse to start unless upsc returns a non-empty status set that
contains OL and no known blocker. The refusal cases are:
- on-battery (
OB) - a critical flag the TUI paints red (
LB/TESTFAIL/COMMBAD/FSD) OLmissing from an otherwise non-blocking status setupscquery or invocation failure (stopped daemon, unknown UPS name, or another fatal NUT error – the message includesupsc’s stderr when it exits non-zero)- an empty or missing
ups.status
Known non-critical advisory states such as OL RB, and unknown tokens
co-present with OL and no known blocker, still pass: the OL flag is
the affirmative utility-power proof, not a guarantee of full battery
health. Example refusal:
$ sudo braid add newdisk=/dev/disk/by-id/ata-TOSHIBA_NEW
error: cannot verify UPS is on utility power (UPS reports on-battery)
-- refusing to start add. Check 'braid ups status', restore utility
power, then retry.
Recovery: run braid ups status to confirm, fix the UPS/NUT state,
restore utility power, wait for the status to return to a trusted OL,
and retry the command.
Two clarifications:
braid doctor’sups_daemon: okmeans the configured NUT daemon is reachable; it is not a guarantee that mutating-command preflight will pass. The refusal error fromadd/remove/remove-missing/replaceis the primary channel for the exact mutation-readiness blocker.- The
OLgate assumes the configured NUT driver reportsOLon utility power as documented by NUT. If a device or driver violates that contract, inspect withbraid ups status; the recovery is to fix the NUT driver/config or disablebraid.upsuntil the UPS state can be trusted.
doctor checks
braid doctor adds two UPS-adjacent checks when UPS support is enabled:
- ups daemon – fails if
upscis missing or cannot be spawned, because braid cannot verify the enabled UPS shutdown path. It warns ifupscruns but cannot reach the daemon or exits non-zero. Fix missingupscby checking the braid wrapper/NUT package path; fix daemon reachability withsystemctl status upsd.service. - braid-online – fails (high severity) if the pool is mounted but
braid-online.serviceis not active. Without that service active, the UPS shutdown path does not unmount the pool, and the safety guarantee silently breaks. Fix by runningsystemctl start braid-online.serviceorbraid unlock.
Both checks skip when UPS support is disabled, and the braid-online check additionally skips when the pool is not mounted (there is nothing for the UPS shutdown path to unmount).
v1 limitation: no async alert
There is no asynchronous notification when the UPS goes on battery or
loses comms in v1. Operators who are not actively watching braid ups status or the TUI will not see those conditions – only the orderly
shutdown on LB is automatic.
This is deliberate: integrating UPS events into braid’s shared alert
model requires splitting AlertCause by persistence semantics
(latched-until-ack for disk errors, active-while-condition-holds for
live UPS states) and is out of scope for v1. See
decisions/020-ups-integration.md
for the open-question status.
If you need asynchronous UPS notifications today, wire NUT’s
NOTIFYCMD directly – braid does not touch it.