← braid

UPS

This guide covers enabling UPS (uninterruptible power supply) support on a braid NAS via NUT (Network UPS Tools).

Enabling UPS support (braid.enable = true plus braid.ups.enable = true) turns on three behaviors:

  • Orderly poweroff on low battery. When the UPS reports critical, NUT’s upsmon invokes systemctl poweroff. systemd unwinds braid-online.service’s ExecStop, which runs braid lock and cleanly unmounts the pool before the battery exhausts.
  • Preflight refusal without verified utility power. braid add / remove / remove-missing / replace check UPS state at startup and refuse to begin a pool mutation unless the UPS reports verified utility power (OL). This narrows the surface that journal recovery needs to cover.
  • Live state visibility. braid ups status (and the TUI Data tab) show the parsed upsc output: status flags, battery charge, runtime remaining, load, estimated watts, input voltage, and device info.

Scope

v1 supports a single USB-connected UPS on the NAS, monitored by the NAS itself (single-host standalone). Non-USB drivers work through the escape hatch but are not tested.

Minimal config

# configuration.nix
{
  braid = {
    enable = true;
    ups.enable = true;
  };
}

Defaults: name = "ups", driver = "usbhid-ups", port = "auto". Rebuild and plug the UPS’s USB cable in; NUT’s auto-detect finds the device.

Override the driver or port for non-USB UPSes:

braid = {
  enable = true;

  ups = {
    enable = true;
    name = "myups";
    driver = "apcsmart";
    port = "/dev/ttyS0";
  };
};

Checking status

# Curated human summary
sudo braid ups status

# Machine-readable JSON (stable shape for scripts)
sudo braid ups status --json | jq .

Example human output:

UPS: ups
Status: OL
Battery: 100%
Runtime: 30m 0s
Load: 17% (56 W estimated)
Input: 120.0 V (transfer 88-142 V)
Device: APC Back-UPS ES 550G
Battery manufactured: 2023/04/12
Last test: Done and passed

The watts line is labeled estimated and omitted entirely if the UPS does not report both ups.load and ups.realpower.nominal.

The --json output serializes the full parsed model. Distinct error sentinels are emitted for the common non-OK cases:

ConditionJSON shapeExit code
UPS reachable with populated ups.statusserialized UpscOutput0
UPS reachable but ups.status emptyserialized UpscOutput plus "warning": "ups_status_empty"0
UPS query failed{"error": "query_failed", "detail": "exit <code>: <stderr>"}1
UPS invocation failed (upsc could not run – missing on PATH, killed by signal, or other runner-level failure){"error": "invocation_failed", "detail": "command failed: upsc ups: <reason>"}1
UPS not enabled{"error": "ups_not_enabled"}0

TUI UPS panel

braid tui’s Data tab gains a UPS row when UPS support is enabled. Status text is color-coded by severity:

  • Green – OL (on utility power).
  • Yellow – OB (on battery, not yet critical).
  • Red – LB / TESTFAIL / COMMBAD / FSD (critical; shutdown imminent or comms-loss).
  • DarkGray – UPS query failed, or no UPS state available yet.

The panel polls on the same 5-second cadence as the TUI fans panel. Press r to refresh both pool and UPS probes immediately.

What happens on low battery

  1. upsmon sees ups.status: OB LB, declares the UPS critical.
  2. upsmon runs its configured SHUTDOWNCMD. braid overrides the nixpkgs default (shutdown now) with systemctl poweroff.
  3. systemd walks its shutdown sequence. braid-online.service stops with ExecStop running braid lock, which unmounts the pool and closes LUKS.
  4. The host powers off before the battery exhausts.

Under the default upsmon timings (POLLFREQ = POLLFREQALERT = 5, FINALDELAY = 5) the window between LB detection and poweroff is ~10 seconds, plus however long braid lock takes. The default battery.runtime.low in most UPS drivers is around 120 seconds, which is enough headroom for a single-disk pool’s clean teardown. Larger pools may need a wider battery.runtime.low (set at the NUT level, not through braid).

Mutation refusal when utility power is not verified

With UPS enabled, braid add / remove / remove-missing / replace refuse to start unless upsc returns a non-empty status set that contains OL and no known blocker. The refusal cases are:

  • on-battery (OB)
  • a critical flag the TUI paints red (LB / TESTFAIL / COMMBAD / FSD)
  • OL missing from an otherwise non-blocking status set
  • upsc query or invocation failure (stopped daemon, unknown UPS name, or another fatal NUT error – the message includes upsc’s stderr when it exits non-zero)
  • an empty or missing ups.status

Known non-critical advisory states such as OL RB, and unknown tokens co-present with OL and no known blocker, still pass: the OL flag is the affirmative utility-power proof, not a guarantee of full battery health. Example refusal:

$ sudo braid add newdisk=/dev/disk/by-id/ata-TOSHIBA_NEW
error: cannot verify UPS is on utility power (UPS reports on-battery)
-- refusing to start add. Check 'braid ups status', restore utility
power, then retry.

Recovery: run braid ups status to confirm, fix the UPS/NUT state, restore utility power, wait for the status to return to a trusted OL, and retry the command.

Two clarifications:

  • braid doctor’s ups_daemon: ok means the configured NUT daemon is reachable; it is not a guarantee that mutating-command preflight will pass. The refusal error from add / remove / remove-missing / replace is the primary channel for the exact mutation-readiness blocker.
  • The OL gate assumes the configured NUT driver reports OL on utility power as documented by NUT. If a device or driver violates that contract, inspect with braid ups status; the recovery is to fix the NUT driver/config or disable braid.ups until the UPS state can be trusted.

doctor checks

braid doctor adds two UPS-adjacent checks when UPS support is enabled:

  • ups daemon – fails if upsc is missing or cannot be spawned, because braid cannot verify the enabled UPS shutdown path. It warns if upsc runs but cannot reach the daemon or exits non-zero. Fix missing upsc by checking the braid wrapper/NUT package path; fix daemon reachability with systemctl status upsd.service.
  • braid-online – fails (high severity) if the pool is mounted but braid-online.service is not active. Without that service active, the UPS shutdown path does not unmount the pool, and the safety guarantee silently breaks. Fix by running systemctl start braid-online.service or braid unlock.

Both checks skip when UPS support is disabled, and the braid-online check additionally skips when the pool is not mounted (there is nothing for the UPS shutdown path to unmount).

v1 limitation: no async alert

There is no asynchronous notification when the UPS goes on battery or loses comms in v1. Operators who are not actively watching braid ups status or the TUI will not see those conditions – only the orderly shutdown on LB is automatic.

This is deliberate: integrating UPS events into braid’s shared alert model requires splitting AlertCause by persistence semantics (latched-until-ack for disk errors, active-while-condition-holds for live UPS states) and is out of scope for v1. See decisions/020-ups-integration.md for the open-question status.

If you need asynchronous UPS notifications today, wire NUT’s NOTIFYCMD directly – braid does not touch it.